Description
| Operating voltage KNX | Bus voltage, <4 mA |
| Operating voltage | 110 – 240 V AC 50 – 60 Hz |
| Frequency | 50 – 60 Hz |
| Stand-by consumption | ~0.5 W |
| Installation type | DIN rail |
| Width | 8 modules |
| Type of connection | Terminal screws | Bus connection: KNX bus terminal |
| Max. cable cross section | Solid wire: 0.5 mm² (Ø 0.8) to 4 mm² | Stranded wire with end sleeve: 0.5 mm² to 2.5 mm² |
| Number of channels | 16 |
| Type of contact | NO contact, 16 A, 3 A |
| Opening width | < 3 mm |
| Incandescent/halogen lamp load | 2000 W |
| Fluorescent lamp load (conventional) parallel-corrected | 1300 W (140 µF) |
| Fluorescent lamp load (conventional) not corrected | 2000 VA |
| Fluorescent lamp load (electronic ballast) | 1200 W |
| Energy saving lamps | 300 W |
| LED lamp < 2 W | 55 W |
| LED lamp 2-8 W | 600 W |
| LED lamp > 8 W | 600 W |
| Inrush current | max. 800 A / 200 µs |
| Voltage output | 240 V AC |
| Switching output | Potential-free |
| Switching of various phases | Possible |
| Suitable for SELV | Yes if all channels switch at SELV |
| C load | |
| Type | Module FIX2 |
| Ambient temperature | -5°C … 45°C |
| Type of protection | IP 20 |
| Protection class | II according to EN 60 669 |